The liquid cooling loop is the coolant circulation path of a liquid cooling system — divided into a primary loop (facility cooling water side) and a secondary loop (IT equipment coolant side). Coolant leaves the CDU (Coolant Distribution Unit), is routed through manifolds to the cold plates in each server, absorbs heat, and returns to the CDU for heat exchange — forming a closed circuit. Loop design (serial/parallel, pipe diameter/flow rate/temperature differential) determines cooling efficiency.
For AI racks (NVL72 and the like), the liquid cooling loop is the core engineering challenge of deployment: the sealing of quick disconnects and cold plates on the secondary side, the supply water temperature and flow rate on the primary side, and air bubble removal in the loop — each affects cooling efficiency and reliability. Acceptance testing of the loop (pressure/leak testing + temperature measurement + flow measurement) is a mandatory procurement check.
| Item | Value / Basis |
|---|---|
| Primary loop | Facility cooling water ↔ CDU |
| Secondary loop | CDU ↔ Cold plates (in-rack) |
| Coolant | Deionized water / glycol solution / dielectric fluid |
| Mandatory acceptance checks | Pressure/leak test · Temperature measurement · Flow measurement |
In GB200/GB300 NVL72 fully liquid-cooled racks, the secondary loop covers 18 compute trays plus 9 NVSwitch trays — cold plates blanket the GPU/CPU/NVSwitch chips. Loop sealing is the biggest risk point: any leaking quick disconnect becomes an incident at Full Load. Acceptance criteria: pressure/leak test + 24-hour static observation.